Power: Difference between revisions
(8 intermediate revisions by the same user not shown) | |||
Line 1: | Line 1: | ||
This page details how the mains power has been installed at the space. | This page details how the mains power has been installed at the space. | ||
==Socket power outages== | |||
All point upstairs (F6) have been labeled with information showing details of how they are feed. This is to allow member to more easily identify which break they may need to reset in the case of power outage at a given socket.<br> | |||
The formats is `[Distribution Board]-[Breaker Number]-[Phase]` | |||
If resetting a breaker does not resolve the power issue please report immediately to [[Team: Infrastructure]] via Discord or email. | |||
[[File:Power socket label.jpeg|600px]] | |||
==F6== | ==F6== | ||
Line 285: | Line 293: | ||
! CABLESIZE !! MCBSIZE !! CIRCUIT !! No. !! PHASE !! !! PHASE !! No. !! CIRCUIT !! MCBSIZE !! CABLESIZE | ! CABLESIZE !! MCBSIZE !! CIRCUIT !! No. !! PHASE !! !! PHASE !! No. !! CIRCUIT !! MCBSIZE !! CABLESIZE | ||
|- | |- | ||
| 2.5mm2 || | | 2.5mm2 || B32 RCBO || TEAM STORAGE ROOM RING || 1 | ||
| style="background-color:#643403; color:#ffffff;" | BR1 || || style="background-color:#643403; color:#ffffff;" | BR7 | | style="background-color:#643403; color:#ffffff;" | BR1 || || style="background-color:#643403; color:#ffffff;" | BR7 | ||
| 19 || || || | | 19 || || || | ||
|- | |- | ||
| 6mm2 || | | 6mm2 || B32 MCB || TEAM STORAGE UPS || 2 | ||
| style="background-color:#000000; color:#ffffff;" | BK1 || || style="background-color:#000000; color:#ffffff;" | BK7 | | style="background-color:#000000; color:#ffffff;" | BK1 || || style="background-color:#000000; color:#ffffff;" | BK7 | ||
| 20 || || || | | 20 || || || | ||
Line 376: | Line 384: | ||
! CIRCUIT | ! CIRCUIT | ||
| || || || || || || || || || Sub Board || 100AMP DOUBLE POLE | | || || || || || || || || || Sub Board || 100AMP DOUBLE POLE | ||
|- | |||
! MCBSIZE | ! MCBSIZE | ||
| || || || || || || || || || B50 || | | | || || || || || || || || || B50 MCB || | | ||
|- | |- | ||
! CABLESIZE | ! CABLESIZE | ||
Line 396: | Line 404: | ||
|- | |- | ||
! CIRCUIT | ! CIRCUIT | ||
| SPARE || AUTOMATED<br>LIGHTS || SPARE || CNC SOCKETS || 30mA trip || COMMUNAL<br> | | SPARE || AUTOMATED<br>LIGHTS || SPARE || CNC SOCKETS || 30mA trip || COMMUNAL LIGHTS<br>EMG LIGHTS OVER DOOR || BLUE ROOM <br> WATER HEATER || BLUE ROOM <br> SOCKETS || 30mA trip || Incoming Feed <br> from New Grid Board | ||
|- | |- | ||
! MCBSIZE | ! MCBSIZE | ||
|N/I || B6 || B16 || B32 || 80amp || B6 || B16 || B32 || 80amp | |N/I || B6 MCB || B16 MCB || B32 MCB || 80amp RCD || B6 MCB || B16 MCB || B32 MCB || 80amp RCD || 100AMP DOUBLE POLE | ||
|- | |- | ||
! CABLESIZE | ! CABLESIZE |
Revision as of 17:30, 27 October 2023
This page details how the mains power has been installed at the space.
Socket power outages
All point upstairs (F6) have been labeled with information showing details of how they are feed. This is to allow member to more easily identify which break they may need to reset in the case of power outage at a given socket.
The formats is `[Distribution Board]-[Breaker Number]-[Phase]`
If resetting a breaker does not resolve the power issue please report immediately to Team: Infrastructure via Discord or email.
F6
DB1 Workshop
This is the new grid feed
NZMB1-A100 In=100A Eaton 100A Triple Pole 25kA MCCB
CABLESIZE | MCBSIZE | CIRCUIT | No. | PHASE | PHASE | No. | CIRCUIT | MCBSIZE | CABLESIZE | |
---|---|---|---|---|---|---|---|---|---|---|
1 | BR1 | BR7 | 19 | |||||||
2 | BK1 | BK7 | 20 | |||||||
3 | GY1 | GY7 | 21 | |||||||
2.5mm2 | C16A MCB | Sander Dusty North |
4 | BR2 | BR8 | 22 | ||||
5 | BK2 | BK8 | 23 | |||||||
6 | GY2 | GY8 | 24 | |||||||
2.5mm2 | C16A MCB | Dust Extractor Dusty Post |
7 | BR3 | BR9 | 25 | Gatekeeper UPS | B6A RCBO | 1.5mm2 | |
8 | BK3 | BK9 | 26 | Lights | B10A RCBO | 4mm2 | ||||
9 | GY3 | GY9 | 27 | Table Saw | B16A RCBO | 4mm2 | ||||
2.5mm2 | C16A MCB | Morticer Woodworking Post |
10 | BR4 | BR10 | 28 | Dusty West/South |
B32A RCBO | 4mm2 | |
11 | BK4 | BK10 | 29 | Dusty North/East |
B32A RCBO | 4mm2 | ||||
12 | GY4 | GY10 | 30 | Woodworking West |
B32A RCBO | 4mm2 | ||||
2.5mm2 | C16A MCB | Bridgeport Metalwork Post |
13 | BR5 | BR11 | 31 | Woodworking East |
B32A RCBO | 4mm2 | |
14 | BK5 | BK11 | 32 | Metalwork West\South |
B32A RCBO | 4mm2 | ||||
15 | GY5 | GY11 | 33 | Metalwork Posts |
B32A RCBO | 4mm2 | ||||
16mm2 | B63A MCB | Metalworking Feed (DB3) | 16 | BR6 | BR12 | 34 | North Wall Spray Booth Laser |
B32A RCBO | 4mm2 | |
17 | BK6 | BK12 | 35 | East Wall Print Room |
B32A RCBO | 4mm2 | ||||
18 | GY6 | GY12 | 36 | Studio Feed (DB2) | B63A MCB | 16mm2 |
DB2 Studio
This board is is on L3, feed from a B63A MCB on the New Workshop board (DB1-36-L3)
10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | MAIN SWITCH | |
---|---|---|---|---|---|---|---|---|---|---|---|
CIRCUIT | Lights | UPS | Members Storage | Studio South Radial | Studio North Ring | Craft | Kitchen | Toilets | Hob | Incoming Feed from Workshop board (DB1-36-L3) | |
MCBSIZE | B310A RCBO | B16A RCBO | B32A RCBO | B32A RCBO | B32A RCBO | B32A RCBO | B32A RCBO | B32A RCBO | B32A RCBO | 100AMP DOUBLE POLE | |
CABLESIZE | 4mm2 | 4mm2 | 4mm2 | 4mm2 | 4mm2 | 4mm2 | 4mm2 | 4mm2 | 4mm2 | 16mm2 |
DB3 Metalworking
Feed from a B63A MCB on the New Workshop board (DB1-16/17/18-L1/L2/L3)
CABLESIZE | MCBSIZE | CIRCUIT | No. | PHASE | PHASE | No. | CIRCUIT | MCBSIZE | CABLESIZE | |
---|---|---|---|---|---|---|---|---|---|---|
1 | BR1 | BR9 | 25 | |||||||
2.5mm2 | B32 | ELECTRONICS SYSTEM E-STOP |
2 | BK1 | BK9 | 26 | ||||
B20 | 3 | GY1 | GY9 | 27 | B32 | |||||
C20 | 4 | BR2 | BR10 | 28 | C40 | |||||
5 | BK2 | BK10 | 29 | B20 | ||||||
6 | GY2 | GY10 | 30 | B32 | ||||||
D?40 | 7 | BR3 | BR11 | 31 | C20 | |||||
8 | BK3 | BK11 | 32 | |||||||
9 | GY3 | GY11 | 33 | |||||||
B20 | 10 | BR4 | BR12 | 34 | C20 | |||||
B32 | 11 | BK4 | BK12 | 35 | ||||||
B32 | 12 | GY4 | GY12 | 36 | ||||||
C20 | 13 | BR5 | BR13 | 37 | C20 | |||||
14 | BK5 | BK13 | 38 | |||||||
15 | GY5 | GY13 | 39 | |||||||
C20 | 16 | BR6 | BR14 | 40 | C20 | |||||
17 | BK6 | BK14 | 41 | |||||||
18 | GY6 | GY14 | 42 | |||||||
2.5mm2 | C20 | BIG BANDSAW | 19 | BR7 | BR15 | 43 | ARC WELDER | D32 | 6mm2 | |
20 | BK7 | BK15 | 44 | |||||||
21 | GY7 | GY15 | 45 | |||||||
2.5mm2 | C20 | DONKEY SAW | 22 | BR8 | BR16 | 46 | TIG WELDER | D63 | 16mm2 | |
23 | BK8 | BK16 | 47 | |||||||
24 | GY8 | GY16 | 48 |
G4 & G5
G4
NZMB1-A100 In=100A Eaton 100A Triple Pole 25kA MCCB
CABLESIZE | MCBSIZE | CIRCUIT | No. | PHASE | PHASE | No. | CIRCUIT | MCBSIZE | CABLESIZE | |
---|---|---|---|---|---|---|---|---|---|---|
2.5mm2 | B32 RCBO | TEAM STORAGE ROOM RING | 1 | BR1 | BR7 | 19 | ||||
6mm2 | B32 MCB | TEAM STORAGE UPS | 2 | BK1 | BK7 | 20 | ||||
3 | GY1 | GY7 | 21 | |||||||
4 | BR2 | BR8 | 22 | |||||||
5 | BK2 | BK8 | 23 | |||||||
6 | GY2 | GY8 | 24 | |||||||
7 | BR3 | BR9 | 25 | |||||||
8 | BK3 | BK9 | 26 | |||||||
9 | GY3 | GY9 | 27 | |||||||
10 | BR4 | BR10 | 28 | |||||||
11 | BK4 | BK10 | 29 | |||||||
12 | GY4 | GY10 | 30 | |||||||
13 | BR5 | BR11 | 31 | |||||||
14 | BK5 | BK11 | 32 | |||||||
15 | GY5 | GY11 | 33 | |||||||
16 | BR6 | BR12 | 34 | |||||||
17 | BK6 | BK12 | 35 | |||||||
18 | GY6 | GY12 | 36 |
G5
New Grid
NZMB1-1-AF63 In=63A Eaton 63A Single Pole 25kA MCCB
This board is is on L1
10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | MAIN SWITCH | |
---|---|---|---|---|---|---|---|---|---|---|---|
CIRCUIT | Sub Board | 100AMP DOUBLE POLE | |||||||||
MCBSIZE | B50 MCB | ||||||||||
CABLESIZE | 6?mm2 |
Sub board
RCD2/4 | RCD2/3 | RCD2/2 | RCD2/1 | RCD2 | RCD1/3 | RCD1/2 | RCD1/1 | RCD1 | MAIN SWITCH | |
---|---|---|---|---|---|---|---|---|---|---|
CIRCUIT | SPARE | AUTOMATED LIGHTS |
SPARE | CNC SOCKETS | 30mA trip | COMMUNAL LIGHTS EMG LIGHTS OVER DOOR |
BLUE ROOM WATER HEATER |
BLUE ROOM SOCKETS |
30mA trip | Incoming Feed from New Grid Board |
MCBSIZE | N/I | B6 MCB | B16 MCB | B32 MCB | 80amp RCD | B6 MCB | B16 MCB | B32 MCB | 80amp RCD | 100AMP DOUBLE POLE |
CABLESIZE | N/C | 1.5mm2 | N/C | 2.5mm2 | 1.5mm2 | 2.5mm2 | 2.5mm2 |
KEY :
N/I - NOT INSTALLED
N/C - NOT CONNECTED
G6
Metalworking
This is on the old grid and is planned to be removed
CABLE SIZE | MCB | CIRCUIT | PHASE | PHASE | CIRCUIT | MCB | CABLE SIZE | |
---|---|---|---|---|---|---|---|---|
RCBO32 30mA TRIP |
TEMP SOCKETS BELOW BOARD |
BR1 | BR7 | RING MAIN |
RCBO32 30mA TRIP |
2.5MM | ||
BK1 | BK7 | STORAGE |
RCBO32 30mA TRIP |
6MM | ||||
GY1 | GY7 | MAIN |
RCBO32 30mA TRIP |
2.5MM | ||||
BR2 | BR8 | |||||||
BK2 | BK8 | |||||||
GY2 | GY8 | |||||||
BR3 | BR9 | |||||||
BK3 | BK9 | |||||||
GY3 | GY9 | |||||||
BR4 | BR10 | |||||||
BK4 | BK10 | |||||||
GY4 | GY10 | |||||||
BR5 | BR11 | |||||||
BK5 | BK11 | |||||||
GY5 | GY11 | |||||||
C63 | BR6 | BR12 | ||||||
BK6 | BK12 | |||||||
GY6 | GY12 |
Corridor
This is on the new grid
NZMB1-A100 In=100A Eaton 100A Triple Pole 25kA MCCB
CABLESIZE | MCBSIZE | CIRCUIT | No. | PHASE | PHASE | No. | CIRCUIT | MCBSIZE | CABLESIZE | |
---|---|---|---|---|---|---|---|---|---|---|
1 | BR1 | BR7 | 19 | MEMBERS STORAGE RING MAIN |
B32 RCBO | 2.5mm2 | ||||
2 | BK1 | BK7 | 20 | UPS MEMBERS STORAGE |
B32 RCBO | 6mm2 | ||||
3 | GY1 | GY7 | 21 | CLASSROOM RING MAIN |
B32 RCBO | 2.5mm2 | ||||
4 | BR2 | BR8 | 22 | CLASSROOM LIGHT CONTROL BOX |
B6 RCBO | 2.5mm2 | ||||
5 | BK2 | BK8 | 23 | |||||||
6 | GY2 | GY8 | 24 | |||||||
7 | BR3 | BR9 | 25 | |||||||
8 | BK3 | BK9 | 26 | |||||||
9 | GY3 | GY9 | 27 | |||||||
10 | BR4 | BR10 | 28 | |||||||
11 | BK4 | BK10 | 29 | |||||||
12 | GY4 | GY10 | 30 | |||||||
13 | BR5 | BR11 | 31 | |||||||
14 | BK5 | BK11 | 32 | |||||||
15 | GY5 | GY11 | 33 | |||||||
16 | BR6 | BR12 | 34 | |||||||
17 | BK6 | BK12 | 35 | |||||||
18 | GY6 | GY12 | 36 |